Leave Your Message

100A RCCB Electromagnetic Circuit Breaker

Introducing the General Earth Fault Protection System, a comprehensive solution for safeguarding against a range of electrical hazards. This innovative system offers reliable protection against the effects of sinusoidal alternating earth fault currents, as well as indirect and direct contacts, reducing the risk of injury and electrical fires. With a focus on insulation fault prevention, this system provides an additional layer of safety to mitigate the risk of fire. The General Earth Fault Protection System is suitable for use in residential and non-residential buildings, energy sources, industrial settings, and infrastructure. Its advanced design and functionality make it an ideal choice for ensuring safety and compliance in various applications. Trust General Earth Fault Protection System to deliver superior protection and peace of mind

    Release

    Type Tripping sensitivity data
    AC For residual sinusoidal alternating currents 30mA For personnel, material and fire protection, as well as for protection against direct contact
    A For residual sinusoidal alternating currents and residual pulsating direct currents 100mA For providing protection against indirect contacts
    S For selectivity, with time delay 300mA For providing fire protection in case of insulation faults
    Wiring Diagramvps

    Wiring Diagram

    Specifications

    Type Standard lEC/EN 61008-1
    Electrical Leakage type Electromagnetic type
    features Rated current In A 16, 25, 32, 40, 50, 63, 80, 100
    Type (wave form of the earth leakage sensed) A, AC
    Poles P 2, 4
    Rated voltage Ue V 230/400
    Insulation voltage Ui V 500
    Rated frequency Hz 50/60
    Rated breaking capacity  Inc=I△c A 6000A
    Rated impulse withstand voltage (1.2/50) Uimp V 6000
    Dielectric test voltage at ind. Freq. for 1min kV 2.5
    Rated sensitivity  IΔn A 0.03, 0.1, 0.3
    Rated residual making and breaking capacity I△m A 500(In≤40A); 630(In=50A/63A);1000(In=80A/100A)
    Pollution degree 2
    Mechanical features Electrical life t 4000
    Mechanical life t 8000
    Protection degree IP20
    Storage temperature -25~+70
    Installation Ambient temperature (with daily average≤35℃) -5~+40
    Terminal connection type Cable/Pin-type busbar
    Terminal size top / bottom for cable mm2 25/35
    AWG 18-3/18-2
    Terminal size top / bottom for busbar mm2 16-10
    AWG 18-8/18-5
    Tightening torque N*m 2.5
    In-Ibs 22
    Mounting On DIN rail EN 60715(35mm)by means of fast clip device
    Connection From top and bottom