Leave Your Message

32 MCB DPN: Miniature Circuit Breaker DPN32A for Electrical Panel

Introducing our latest product, the [Company Name] circuit breaker. With overload protection and short circuit protection, our circuit breaker is designed to keep your electrical systems safe and secure. It is suitable for use in residential buildings, non-residential buildings, energy source industries, and infrastructure. Our circuit breaker offers precise controlling and is classified according to the type of instantaneous release, with options including type B(3-5)ln, type C(5-10)ln, and type D(10-20)ln. This versatility allows for tailored protection based on your specific needs. Trust in our [Company Name] circuit breaker to provide reliable and effective protection for your electrical systems
    63 RCCB Electromagnetict4c

    General

    1. Overload protection
    2. Short circuit protection
    3. Controlling
    4. Used in residential building, non-residential building, energy source industry and infrastructure.
    5. According to the type of instantaneous release classified as follows : type B(3-5)ln, type C(5-10)ln

    Product Details

    Type Test current Tripping time Expected result Type Test current Tripping time Expected result
    B,C 1.13In t≤1h(In≤63A) Not tripping B 3In t≤0.1s Not tripping
    1.13In t≤2h(In>63A) Tripping
    C 5In t≤0.1s
    B,C 1.45In t<1h(In≤63A) Tripping
    1.45In t<2h(In>63A) B 5In t<0.1s Tripping
    B,C 2.55In 1s<t<60s(In≤32A)
    C 10In t<0.1s
    2.55In 1s<t<120s(In>32A)
    Curven1r

    Specifications

    Type Standard lEC/EN 60898-1
    Electrical features Rated current ln A 6, 10, 16, 20, 25, 32
    Poles P 1P+N
    Rated voltage Ue V 230
    Insulation voltage Ui V 500
    Rated frequency Hz 50/60
    Rated breaking capacity A 3000
    Rated impulse withstand voltage(1.2/50)Uimp V 4000
    Dielectric test voltage at ind. Freq. for 1min kV 2
    Pollution degree 2
    Thermo-magnetic release characteristic B, C
    Mechanical features Electrical life t 4000
    Mechanical life t 10000
    Protection degree IP20
    Reference temperature for setting of thermal element 30
    Ambient temperature -5~+40
    (with daily average≤35℃)
    Storage temperature -25~+70
    Installation Terminal connection type Cable/Pin-type busbar
    Terminal size top / bottom for cable mm2 16
    AWG 5月18日
    Terminal size top / bottom for busbar mm2 10
    AWG 5月18日
    Tightening torque N*m 2
    In-Ibs 18
    Mounting On DIN rail EN 60715(35mm)by means of fast clip device
    Connection From top or bottom