Leave Your Message

40 Amp RCBO Electromagnetic Circuit Breaker

Introducing our General line of circuit protection devices, designed to safeguard residential buildings against a variety of electrical hazards. Our products offer reliable protection against overload and short-circuit currents, as well as the effects of sinusoidal alternating earth fault currents. Additionally, our devices provide protection against indirect contacts and offer additional protection against direct contacts. With a focus on fire hazard prevention caused by insulation faults, our General line of circuit protection devices ensures the safety and security of the electrical systems in your home. Available in various types of instantaneous release, including type B (3-In and type C (5-10) In, our products are designed to meet a wide range of electrical safety needs. Trust our company name for quality and reliability in circuit protection

    Release

    Type Test current Tripping time Expected result
    B,C 1.13In t≤1h(In≤63A) Not tripping
    1.13In t≤2h(In>63A)
    B,C 1.45In t<1h(In≤63A) Tripping
    1.45In t<2h(In>63A)
    B,C 2.55In 1s<t<60s(In≤32A) Tripping
    2.55In 1s<t<120s(In>32A)
    B 3In t≤0.1s Not tripping
    C 5In t≤0.1s
    B 5In t<0.1s Tripping
    C 10In t<0.1s

    Curve

    40 RCBO Electromagnetic (2)opk

    Specifications

    Type Standard IEC/EN 61009-1
    Electrical features Leakage type Electromagnetic type
    Rated current In A 6,10,16,20,25,32,40
    Type (wave form of the earth leakage sensed) A,AC
    Poles P 1P+N
    Rated voltage Ue V 230
    Insulation voltage Ui V 500
    Rated frequency Hz 50/60
    Rated breaking capacity Icn A 6000
    Rated impulse withstand voltage (1.2/50)Uimp V 4000
    Dielectric test voltage at ind.Freq.for 1min kV 2
    Rated sensitivity I△n A 0.03,0.05,0.1
    Break time under I△n S ≤0.1
    Rated residual making and breaking capacity I△m A 500
    Pollution degree 2
    Mechanical features Electrical life t 4000
    Mechanical life t 8000
    Protection degree IP20
    Storage temperature -25~+70
    Ambient temperature (with daily average≤35℃) -5~+40
    Installation Terminal connection type Cable/U-type bar/Pin-type busbar
    Terminal size top/bottom for cable   mm² 16
      AWG 18-5
    Terminal size top/bottom for busbar   mm2 16
      AWG 18-5
    Tightening torque   N*m 1.2
    In-Ibs 11
    Mounting On DIN rail EN 60715(35mm)by means of fast clip device
    Connection From top and bottom