63 RCBO Electronic: Safety Switch for Electrical Protection

Introducing the General series of circuit breakers, designed to provide comprehensive protection for residential buildings. With a focus on safeguarding against overload, short-circuit currents, earth faults, and insulation faults, the General series offers peace of mind for homeowners. With its innovative design, it also provides protection against indirect and direct contacts, as well as the risk of fire hazard. The General series is available in various types of instantaneous release, including Type B, Type C, and Type D, to cater to different protection needs. Manufactured by [Company Name], a trusted name in electrical solutions, the General series is a reliable and efficient choice for ensuring the safety and security of residential spaces

    Release

    Type Test current Tripping time Expected result Type Test current Tripping time Expected result
    B,C,D 1.13In t≤1h(In≤63A) Not tripping B 3In t≤0.1s Not tripping
    1.13In t≤2h(In>63A) C 5In t≤0.1s
    B,C,D 1.45In t<1h(In≤63A) Tripping D 10In t≤0.1s
    1.45In t<2h(In>63A) B 5In t<0.1s Tripping
    B,C,D 2.55In 1s<t<60s(In≤32A) Tripping C 10In t<0.1s
    2.55In 1s<t<120s(In>32A) D 20In t<0.1s

    Curve

    63 RCBO Electronic (2)ots

    Specifications

    Type Standard IEC/EN 61009-1
    Electrical features Poles P 1P+N, 2, 3, 3P+N, 4
    Type(wave form of the earth leakage sensed) AC
    Thermo-magnetic release characteristic B, C, D
    Rated current In A 6, 10, 16, 20, 25, 32, 40, 50, 63
    Rated voltage Ue V 230V AC(1P+N, 2P)  400V AC(3P, 3P+N, 4P)
    Rated sensitivity lΔn A 0.03, 0.05, 0.1, 0.3
    Rated residual making and A 500(In≤40A) 630(In>40A)
    breaking capacity lΔm
    Rated short-circuit capacity lcn A 4500
    Break time under lΔn s ≤0.1
    Rated frequency Hz 50/60
    Rated impulse withstand voltage(1.2/50)Uimp V 4000
    Dielectric test voltage at ind.Freq.for 1min kV 2
    Insulation voltage Ui V 500
    Pollution degree 2
    Mechanical features Electrical life t 4000
    Mechanical life t 10000
    Contact position indicator Yes
    Protection degree IP20
    Ambient temperature(with daily average≤35℃) -5~+40
    Storage temperature -25~+70
    Installation Terminal connection type Cable/Pin-type busbar
    Terminal size top/bottom for cable mm² 25
    AWG 18-3
    Terminal size top/bottom for busbar mm² 25
    AWG 18-3
    Tightening torque N*m 2
    In-Ibs 18
    Mounting On DIN rail EN60715(35mm)by means of fast clip device
    Connection From top

    Leave Your Message