Leave Your Message

63N MCB: Miniature Circuit Breaker for Household Use

Introducing the YCB7-63N series miniature circuit breaker, designed for efficient overcurrent protection in AC 50/60Hz, rated voltage 230V/400V circuits with a rated current of up to 63A. These circuit breakers provide isolation, overload, and short circuit protection, making them suitable for a wide range of applications in industry, commerce, high-rise buildings, and residential buildings. The breakers are compliant with the IEC/EN 60898-1 standard, ensuring high quality and reliability. With a focus on safety and performance, these circuit breakers are an ideal choice for protecting building line facilities and other similar purposes. Trust in the YCB7-63N series to provide the protection and peace of mind you need for your electrical circuits

    Selection

    YCB7 - 63 N 1P C 16
    Model Shell grade current Breaking capacity Number of poles Tripping Rated curren
    characteristics
    Miniatur circuit breaker e 63 N:6kA 1P B 1
    2P C 2
    3P D 4
    4P 6
    10
    16
    20
    25
    32
    40
    50
    63
    80

    Note:This product can be assembled with accessories(YCB7-63N  OF/SD/OF+SD/ MX/ MVMN/MX+OF, etc)

    63N MCB (2)082

    Technical data

    Type Standard IEC/EN 60898-1
    Comprehensive data Function Overload, Short circuit, Isolation
    Number of poles 1P,2P,3P,4P
    Rated current In A 1-63A
    Rated frequency Hz 50/60Hz
    Electrical features Rated voltage Ue V 230/400
    Rated insulation voltage Ui V 500
    Rated breaking capacity Icn A 6000
    Rated impulse withstand voltage Uimp(1.2/50) kA 4
    Pollution degree 2
    Use category II、III
    Trip type Thermal magnetic release
    Thermal magnetic tripping characteristics B,C,D
    Electrical and mechanical accessories
    Mechanical features Mechanical life Times 20000
    Electrical life Times 10000
    Protection degree IP20
    Antihumidity and heat resistance The relative humidity of the air is not more than 50% when the ambient air temperature is +40°C, and it can have a higher relative humidity at a lower temperature
    Reference ambient temperature °C 30
    Ambient temperature °C -5°C-+40°C, the average value of 24h does not exceed +35°C
    Height m Not exceeding 2000
    Installation Terminal connection type Cable/Pin-type busbar
    Maximum Terminal size mm² 25
    wire capacity top/bottom for cable AWG 18-3
    Terminal size mm² 25
    top/bottom for busbar AWG 18-3
    Torque N*m 2
    In-lbs 18
    Tool 18 Phillips screwdriver or flat-blade screwdriver
    Installation On DIN rail EN 60715 (35mm) by means of fast clip device
    Wiring method From top or bottom
    63N MCB (3)ul3

    Selection

    Type Test current Tripping time Expected result Type Test current Tripping time Expected result
    B,C,D 1.13In t≤1h(In≤63A) Not tripping B 3In t≤0.1s Not tripping
    1.13In t≤2h(In>63A) C 5In t≤0.1s
    B,C,D 1.45In t<1h(In≤63A) Tripping D 10In t≤0.1s
    1.45In t<2h(In>63A) B 5In t<0.1s Tripping
    B,C,D 2.55In 1s<t<60s(In≤32A) Tripping C 10In t<0.1s
    2.55In 1s<t<120s(In>32A) D 20In t<0.1s