Leave Your Message

CCB6Z-63 Miniature Circuit Breaker - 63 MCB

Introducing our innovative product designed for overload and short circuit protection in residential and non-residential buildings, as well as the energy source industry and infrastructure. Our product offers precise controlling and is available in various types of instantaneous release including type B (3-5)ln, type C (5-10)ln, and type D (10-20)ln, ensuring comprehensive protection for a wide range of electrical systems. With our reliable and efficient protection, you can have peace of mind knowing that your electrical systems are safeguarded against potential hazards. Trust in our company name for high-quality, durable, and effective protection solutions. Choose our product for superior overload and short circuit protection in a variety of settings
    ccb6z-63 miniature circuit breaker - 63 mcb (4)

    General

    1. Overload protection
    2. Short circuit protection
    3. Controlling
    4. Used in residential building, non-residential building, energy source industry and infrastructure.
    5. According to the type of instantaneous release classified as follows: type B(3-5)ln, type C(5-10)ln, type D(10-20)ln

    Release

    Type Test curren Tripping time Expected result Type Test current Tripping time Expected result
    B,C,D 1.13In t≤1h(In≤63A) Not tripping B 3In t≤0.1s Not tripping
    1.13In t≤2h(In>63A) C 5ln t≤0.1s
    B,C,D 1.45In t<1h(In≤63A) Tripping D 10ln t≤0.1s
    1.45ln t<2h(In>63A) B 5ln t<0.1s Tripping
    B,C,D 2.55In 1s<t<60s(In≤32A) Tripping C 10ln t<0.1s
    2.55ln 1s<t<120s(In>32A) D 20ln t<0.1s
    YCB6H-63 MCB (2)wcw

    Overall And Mounting Dimensions(mm)

    Specifications

    Type Standard IEC/EN 60898-1
    Electrical features Rated current In A 1, 2, 3, 4, 6, 10, 16,20,25,32,40,50, 63
    Poles P 1, 2, 3,4
    Rated voltage Ue V 230/400
    Insulation voltage Ui V 500
    Rated frequency Hz 50/60
    Rated breaking capacity A 4500
    Rated impulse withstand voltage(1.2/50)Uimp V 4000
    Dielectric test voltage at ind. Freq.for 1min kV 2
    Pollution degree 2
    Thermo-magnetic release characteristic B, C,D
    Mechanical features Electrical life t 6000
    Mechanical life t 20000
    Protection degree IP20
    Reference temperature for setting of thermal element 30
    Ambient temperature(with daily average≤35℃) -5~+40
    Storage temperature -25~+70
    Installation Terminal connection type Cable/Pin-type busbar
    Terminal size top / bottom for cable mm2 25
    AWG 18-3
    Terminal size top / bottom for busbar mm2 25
    AWG 18-3
    Tightening torque N*m 2
    In-1bs 18
    Mounting On DIN rail EN 60715(35mm)by means of fast clip device
    Connection From top or bottom