CCB6HLN-63 RCBO Electronic: Circuit Breaker with Overload Protection

Introducing our latest general protection circuit breaker, designed to provide comprehensive safety measures for residential buildings. Our product offers protection against overload and short-circuit currents, as well as the effects of sinusoidal alternating earth fault currents and insulation faults to minimize the risk of fire hazards. Additionally, it ensures protection against indirect contacts and provides additional protection against direct contacts. The circuit breaker is available in different types with varying instantaneous release classifications, including type B, C, and D, to suit different needs and preferences. Our company is proud to offer a reliable and efficient solution for ensuring the safety and security of electrical systems in residential buildings. Trust our general protection circuit breaker to keep your home and loved ones safe

    Release1

    Type Test current Tripping time Expected result
    B,C,D 1.13In t≤1h(In≤63A) Not tripping
    1.13In t≤2h(In>63A)
    B,C,D 1.45In t<1h(In≤63A) Tripping
    1.45In t<2h(In>63A)
    B,C,D 2.55In 1s<t<60s(In≤32A) Tripping
    2.55In 1s<t<120s(In>32A)

    Release2

    Type Test current Tripping time Expected result
    B 3In t≤0.1s Not tripping
    C 5In t≤0.1s
    D 10In t≤0.1s
    B 5In t<0.1s Tripping
    C 10In t<0.1s
    D 20In t<0.1s

    Curve

    YCB6HLN-63 RCBO Electronic (2)sfd

    Specifications

    Type Standard IEC/EN 61009-1
    Electrical Poles P 1P+N
    features Type(wave form of the earth leakage sensed) AC
    Thermo-magnetic release characteristic B, C, D
    Rated current In A 6, 10, 16, 20, 25, 32, 40, 50, 63
    Rated voltage Ue V 230
    Rated sensitivity lΔn A 0.03, 0.05, 0.1
    Rated residual making and A 500(In≤40A) 630(In>40A)
    breaking capacity lΔm
    Rated short-circuit capacity lcn A 4500
    Break time under lΔn s ≤0.1
    Rated frequency Hz 50/60
    Rated impulse withstand voltage(1.2/50)Uimp V 4000
    Dielectric test voltage at ind.Freq.for 1min kV 2
    Insulation voltage Ui V 500
    Pollution degree 2
    Mechanical features Electrical life t 4000
    Mechanical life t 10000
    Contact position indicator Yes
    Protection degree IP20
    Ambient temperature(with daily average≤35℃) -5~+40
    Storage temperature -25~+70
    Installation Terminal connection type Cable/Pin-type busbar
    Terminal size top/bottom for cable mm² 25
    AWG 18-3
    Terminal size top/bottom for busbar mm² 25
    AWG 18-3
    Tightening torque N*m 2
    In-Ibs 18
    Mounting On DIN rail EN60715(35mm)by means of fast clip device
    Connection From top