Our company offers a range of protection products designed to ensure the safety of personnel and prevent fire hazards. Our cable and line protection systems provide reliable protection against overload and short-circuits, minimizing the risk of electrical fires. With options for different levels of sensitivity, our products offer additional protection in the event of direct contact or ground fault currents, with tripping ensured for sinusoidal, alternating currents. Our innovative designs and high-quality materials make our products ideal for a wide range of applications, from residential to industrial settings. Trust our protection solutions to keep your personnel safe and your premises secure from fire hazards

    Release1

    Type Tripping time I△n(A) Expected result Note
    I△n 2I△n 5I△n 6I△n
    General 63,80,100,125 ≥0.03 0.1 0.07 0.04 0.04 Minimum time for tripping
    Time delay Time limit for not tripping 0.06s ≥0.03 0.3 0.2 0.15 0.15 Minimum time for tripping
    ≥0.03 0.13 0.06 0.05 0.04 Minimum time for not tripping
    0.1s ≥0.03 0.6 0.4 0.3 0.2 Minimum time for tripping
    ≥0.03 0.23 0.1 0.06 0.05 Minimum time for not tripping

    Release2

    Type Test current Tripping time Expected result
    C,D 1.05In t≤1h(In≤63A),t≤2h(In≤63A) Not tripping
    C,D 1.3In t≤1h(In≤63A),t≤2h(In≤63A) Tripping
    C,D 2.55In 1s<t<120s Tripping
    C 8In ×80% t≤0.2s Not tripping
    D 12In ×80% t≤0.2s Not tripping
    C 8In × 120% t<0.2s Tripping
    D 12In × 120% t<0.2s Tripping

    Specifications

    Type Standard IEC/EN 60947-2
    Electrical features Type (wave form of the earth leakage sensed) AC
    Thermo-magnetic release characteristic (C)Ii=8In,(D)Ii=12In
    Rated current In A 63, 80, 100
    Poles 1P+N, 2P, 3P, 3P+N, 4P
    Rated voltage Ue V 230/400
    Rated sensitivity IΔn A 0.03, 0.1, 0.3
    Rated short-circuit capacity lcn A 6000
    Mechanical features Break time under I△n s ≤0.1
    Rated impulsewithstand voltage (1.2/50)Uimp V 4000
    Dielectric TEST voltage at ind. Freq. for 1min kV 1.89
    Insulation voltage Ui V 500
    Pollution degree 3
    Electrical life 1500
    Mechanical life 8500
    Contact position indicator Yes
    Protection degree IP20
    Ambient temperature(with daily average≤35℃) -5… +40
    Storage temperature -25… +70
    Installation Terminal connection type Cable/Pin-type busbar
    Terminal size top/bottom for cable mm² 16~50
    AWG 6-1/0
    Terminal size top/bottom for busbar mm² 16~35
    AWG 6-2
    Tightening torque N·m 3.5
    In-Ibs. 31
    Mounting Connection On DIN rail EN 60715 (35mm) by means of fast clip device From top

    Overall And Mounting Dimensions(Mm)

    YCB7LE-125 RCBO Electronic (2)uj3