0102030405
CCB9RL-100 RCCB Electromagnetic - High Quality Protection
Release
| Type | Tripping sensitivity data | ||
| AC | For residual sinusoidal alternating currents | 30mA | For personnel,material and fire protection,as well as Tor protection against airect contact |
| A | For residual sinusoidal alternating currents and residual pulsating direct currents | 100mA | For providing protection against indirect contacts |
| S | For selectivity,with time delay | 300mA | For providing fire protection in case of insulation faults |
Wiring Diagram
Specifications
| Type | Standard | IEC/EN 61008-1 | |
| Electrical features | Leakage type | Electromagnetic type | |
| Rated current In | A | 16,25,32,40,50,63,80,100 | |
| Type (wave form of the earth leakage sensed) | A,AC | ||
| Poles | P | 1P+N,3P+N | |
| Rated voltage Ue | V | 230/400 | |
| Insulation voltage Ui | V | 500 | |
| Rated frequency | Hz | 50/60 | |
| Rated breaking capacity Inc=l4c | A | 600,010,000 | |
| Rated impulse withstand voltage (1.2/50)Uimp | V | 6000 | |
| Dielectric test voltage at ind.Freq.for 1min | kV | 2.5 | |
| Rated sensitivity I△n | A | 0.03,0.1,0.3 | |
| Rated residual making and breaking capacity l-m | A | 500(ln≤40A);630(In=50A/63A);1000(In=80A/100A) | |
| Pollution degree | |||
| Electrical life | t | 4000 | |
| Mechanical features | Mechanical life | t | 8000 |
| Protection degree | IP20 | ||
| Storage temperature | ℃ | -25~+70 | |
| Ambient temperature(with daily average≤35℃) | ℃ | -5~+40 | |
| Terminal connection type | Cable/Pin-type busbar/U-type busbar | ||
| Installation | Terminal size top /bottom for cable | mm² | 25/35 |
| AWG | 18-3/18-2 | ||
| Terminal size top /bottom for busbar | mm² | 16/10 | |
| AWG | 18-8/18-5 | ||
| Tightening torque | N*m | 2.5 | |
| In-Ibs | 22 | ||
| Mounting | On DIN rail EN 60715(35mm)by means of fast clip | ||
| Connection | From top or bottor |