Leave Your Message

CCM8C Molded Case Circuit Breaker

CCM8C series external circuit breakers are suitable for distribution networks with AC 50Hz or 60Hz, rated insulation voltage of 1000V, rated voltage of 400V and below, and rated current of 1000A. Under normal circumstances, the circuit breaker can be used for the infrequent on-off control of the line and the infrequent start of the

motor respectively.
Standard:IEC60947-2;IEC60947-1;

    product detail

    General

    YCM8C series external circuit breakers are suitable for distribution networks with AC 50Hz or 60Hz, rated insulation voltage of 1000V, rated voltage of 400V and below, and rated current of 1000A. Under normal circumstances, the circuit breaker can be used for the infrequent on-off control of the line and the infrequent start of the motor respectively.

    Standard:IEC60947-2;IEC60947-1;

     

    Operating Conditions

    1. Extreme temperature range for storage and transportation: -10°C to 85°C;

    2. Operating range: -10°C to 75°C;

    3. Reference temperature: 55°C;

    4. Atmospheric conditions: The maximum temperature is 75 ℃ and the maximum relative humidity is 95%;

    5. External  magnetic  fields  at  the  installation  site  must  not  exceed  5  times  the strength of the earth's magnetic field, and the product should be kept away from strong  electromagnetic  interference  (such  as  high-power  motors  or  inverters). There should be no explosive or corrosive gases, no exposure to rain or snow, and the environment should be dry and well-ventilated;

    6. Pollution level: level 3; installation category: category III.

    Technical data

     

    Frame current Inm(A)

    250S

    400S

    630S

    800S

    1000S

    Working voltage Ue(V)

    400

    Rated insulation voltage Ui(V)

    AC1000

    Rated impulse withstand voltage Uimp(KV)

    8

    Number of poles (P)

    3

    Rated current In(A)

    100,125,140,160,

    180,200,225,250

    250,315,350,400

    400,500,630

    630,700,800

    800,1000

    Ultimate breaking capacity Icu (KA)

    AC240V

    35

    50

    50

    65

    65

    AC415V

    25

    35

    35

    40

    40

    Operating breaking capacity Ics (KA)

    AC240V

    35

    50

    50

    65

    65

    AC415V

    25

    25

    25

    40

    40

    Electrical life (times)

    1000

    1000

    1000

    500

    500

    Mechanical life (times)

    7000

    4000

    4000

    2500

    2500

    Operating voltage

    AC230V(85%~110%)

    Wiring

    Up in and down out,down in and up out

    Protection degree

    IP30

    Isolation function

    Yes

    Tripping type

    Thermomagnetic

    Accessories

    Shunt,alarm,auxiliary

    Certificate

    CE

    Product feature configuration

    The operation interface of the electric operating mechanism is shown in Figure 1

    1. Circuit breaker status indication window

    2. Mechanism lock

    3. Tripping button

    4. Power and control wiring ports

    5. Manual and automatic switching of cover plates