Leave Your Message

CJX2s AC Contactor

CJX2s series AC Contactor with novel appearance and compact structure is suitablefor using starting &controlling the AC motor frequently,switching on and off thecircuitat a long distance.It is used in combinationwith thermal relay to compose amagneticmotor starter
StandardIEC60947-1,IEC 60947-4-1.

    Product Overview

    CJX2s series AC Contactor with novel appearance and compact structure is suitable for using starting & controlling the AC motor frequently, switching on and off the circuit at a long distance. It is used in combination with thermal relay to compose a magnetic motor starter.
    Standard: IEC 60947-1, IEC 60947-4-1.

    Specifications

    Rated operation current(Ie): 9-95A;
    Rated operation voltage(Ue): 220V~690V;
    Rated insulation voltage: 690V; Poles: 3P;
    Installation: Din rail and screw installation.

    Operating and Installation Conditions

    Type Operating and Installation Conditions
    Installation category III
    Pollution level 3
    Protection degree CJX2s-09~38: IP20; CJX2s-40~95: IP10
    Ambient temperature limit of temperature: -35℃~+70℃,normal temperature: -5℃~+40℃,The average no more than +35℃ within 24 hours.
    Altitude ≤2000m
    Ambient temperature The maximum temperature is 70 degrees, the relative humidity of the air does not exceed 50%, and the temperature below 50% can allow higher relative humidity. If the temperature is 20℃, the air relative  humidity could up to 90%, Special measures should betaken for occasional condensation due to humidity changes.
    Installation position Inclination between installation surface and vertical surface should not exceed ±5°
    Shock vibration Products should be installed and used without significant shake, shock and vibration.

    Overall and Mounting

    CJX2s-09~38

    cjx2s-product-description7

    CJX2s-40~95

    cjx2s-product-description8

    Specifications

    Appearance  CJX2s (1)  CJX2s (2)  CJX2s (3)  CJX2s (4)
    Type CJX2s-09 CJX2s-12 CJX2s-18 CJX2s-25 CJX2s-32 CJX2s-38 CJX2s-40 CJX2s-50 CJX2s-65 CJX2s-80 CJX2s-95
    Main circuit characteristic
    Poles 3P
    Rated insulation voltage(Ui) V 690
    Rated operating voltage(Ue) V 380/400, 660/690
    Rated thermal current(Ith) ,AC-1 20 20 32 40 50 50 50 60 80 125 125
    Rated
    operation
    current(Ie)
    AC-3,380/400V A 9 12 18 25 32 38 40 50 65 80 95
    AC-3,660/690V A 6.6 8.9 12 18 22 22 34 39 42 49 49
    AC-4,380/400V A 3.5 5 7.7 8.5 12 14 18.5 24 28 37 44
    AC-4,660/690V A 1.5 2 3.8 4.4 7.5 8.9 9 12 14 17.3 21.3
    Rated
    operational
    power(Pe)
    AC-3,380/400V kW 4 5.5 7.5 11 15 18.5 18.5 22 30 37 45
    AC-3,660/690V kW 5.5 7.5 10 15 18.5 18.5 30 33 37 45 45
    AC-4,380/400V kW 1.5 2.2 3.3 4 5.4 5.5 7.5 11 15 18.5 22
    AC-4,660/690V kW 1.1 1.5 3 3.7 5.5 6 7.5 10 11 15 18.5
    Mechanical life 10000
    times
    1200 1000 900 650
    Electrical life AC-3 110 90 65
    AC-4 22 22 17 11
    Frequency
    of operation
    AC-3 times/
    hour
    1200 600
    AC-4 300 300
    Connecting capability of main circuit terminal
    Flexible wire 1 wire                   mm² 1…4 1.5…6 2.5…25 4…50
    No terminal 2 wire mm² 1…4 1.5…6 2.5…16 4…25
    Flexible wire 1 wire mm² 1…4 1…6 2.5…25 4…50
    With terminals 2 wire mm² 1…2.5 1…4 2.5…10 4…16
    Hard wire 1 wire mm² 1…4 1.5…6 1.5…10 2.5…25 4…50
    No terminal 2 wire mm² 1…4 1.5… 2.5…10 4…25
    Fastening torque N·m 1.2 1.8 5 9
    Coil
    Rated control
    voltage(Us)
    50Hz V 24、36、48、110、127、220/230、240、380/400、415、440
    50/60Hz V 24、36、48、110、127、220/230、240、380/400、415、440
    Allowed control
    circuit voltage(Us)
    Operation V Installation inclination angle ±22.5°: 85%~110%Us;   Installation inclination angle±5°: 70%~120%
    Release V Installation inclination angle ±22.5°: 20%~75%Us;Installation inclination angle±5°: 20%~65%
    Power
    consumption
    of coil
    Actuation VA 60 70 200 200
    Keep VA 6-9.5 6-9.5 15-20 15-20
    Consumption W 1-3 1-3 6-10 6-10
    Auxiliary contacts
    Auxiliary contacts specification A 11
    Rated thermal current (Ith) A 10
    Rated operating
    voltage (Ue)
    AC V 380
    DC V 220
    Rated control
    capacity
    AC-15 VA 360
    DC-13 W 33
    Certification                                                                                                                            CE, TUV, CB

                

     Type Amax Bmax Cmax a b c d e f
    CJX2s-09, 12, 18 74.5 45.5 85.5 35 50/60 - - - -
    CJX2s-25, 32, 38 83 56.5 97 40 50/70 - - - -
    CJX2s-40, 50, 65 127.5 74.5 117 - - 105 40 100/110 59
    CJX2s-80, 95 127.5 85.5 125.5 - - 105 40 100/110 67