Three Phase Voltage Monitoring Relay

 • monitoring of 3-phase mains:
- voltage in 2 levels (undervoltage and overvoltage) in range 120-277 V (3P+N) or 280-480 V (3P3W )
- phase asymmetry (can be switched off )
- phase sequence
- phase failure
• M480: for circuits 3x 400 V (without neutral)
• M277: for circuits 3x 400 / 230 V (with neutral)
• output contact: 1x changeover 8 A/250 V AC1
• 1-MODULE, DIN rail mounting

    Technical parameters DV5-03~12/M480 DV5-03~12/M277
    Supply    
    Supply terminals: L1/L2/L3 L1/L2/L3/N
    Supply voltage:
    (AC 50 - 60 Hz)
    208-220-230-240-380
    400-415-440-460-480
    120-127-132-138-220
    230-240-254-265-277
    Consumption max.: 5 VA / 2. 10 V, AC 230 V, AC 400 V),
    2 V 4 W (A A / 1. C/DC 24 V)
    Max. dissipated power
    (Un + terminals):
    6.5 W (110 V, 230 V, 400 V),
    5.5 W (24 V)
    Supply voltage tolerance:   -15%;+10%
    Measuring circuit
    Voltage set: 3x 400 V / 50 - 60 Hz 3x 400 V / 230 V / 50 - 60 Hz
    Monitored terminals: L1, L2, L3 L1, L2, L3, N
    Upper voltage level: 240 - 480 V 138 - 276 V
    Bottom voltage level: 35-99% Umax
    Max. permanent overload: 600 V 332V
    Hysteresis: 2 % of set value
    Asymmetry: 5 - 20 %
    Peak overload < 1 ms: 650V < 1 ms 350 V < 1 ms
    Time delay t1: fixed, max.200ms
    Time delay t2: fixed 2s or adjustable 0.1-10 s
    Accuracy
    Set. accuracy (mechanical): 5%
    Repeat accuracy: < 1 %
    Temperature dependance: < 0.1 % / °C (°F)
    Limit values tolerance: 5%
    Output
    Number of contacts: 1x changeover / SPDT
    Rated current: 8 A / AC1
    Switching capacity: 2000 VA / AC1, 192 W / DC
    Inrush current: 12 A / < 3 s
    Switching voltage: 250 V AC1 / 24 V DC
    Mechanical life: 3x107
    Electrical life (AC1): 0.7x10⁵
    Other informatio
    Operating temperature:  -30 to 70
    Storage temperature:  -45 to 85
    Electrical strength: 4 kV (supply-output)
    Operating position: any
    Mounting: DIN rail EN 60715
    Protection degree: IP40 from front panel / IP20 terminals
    Overvoltage category: III.
    Pollution degree: 2
    Max. cable size (mm²): solid wire max. 1x2.5 or 2x1.5 /
    with sleeve max. 2x1.5 (AWG 14 )
    Dimensions: 90x18x70 mm
    Weight: 80 g 78 g
    Standards: IEC60947-5-1 EN 60255-6, EN 61010-1
    Packing Details : Box DIM:505x230x189, QTY:100Pcs, GW:9.1kg

    Description

    description

    Description and importance of functions code

    Function
    code
    Over
    voltage
    Under
    voltage
    Under
    voltage
    Delay
    time
    Phase
    seqUsnce
    Phase
    fail
    Reset delay time
    03         1s
    04 2%...20% -20%...2%   0.1s...10s   1s
    05 2%...20% -20%...2%   0.1s...10s 1s
    06 2%...20% -20%...2% 5%...15% 2s   1s
    07 2%...20% -20%...2% 5%...15% 2s 1s
    08 2%...20% -20%...2% 12.5% , 2s 0.1s...10s   1s
    09 2%...20% -20%...2% 12.5% , 2s 0.1s...10s 1s
    10 15% -15% 12.50% 2s 1s
    11 15% -15% 12.50% 2s   1s
    12 15% -15%   2s 1s
    Note: the function is available

    Connection

    connection

    Symbol

    Symbol

    Function

    Function

    Connection

    connection

    Relay is designated to monitor 3-phase circuits. Type N230 controls voltage towards neutral wire, type A400 controls inter phase voltage. Relay can monitor voltage in two levels (overvoltage / undervoltage), phase asymetry, phase sequence and phase failure. Each faulty state is indicated by individual LED.

    Time delays t1(fixed) - when changing from faulty to normal state or when de-energized and t2 when changing from normal to faulty state. These delays prevent incorrect conduct and oscillation of output device during short voltage peaks in the main or during gradual voltage decline into normal.

    Voltage control
    Set upper level Umax in range Us×(1+5%)-Us×(1+30%) and lower level Umin in range Us×(1-5%)-Us×(1-30%) Umax. In case any phase passes this range, after a delay which eliminated short voltage peaks, contact opens. Output contact again switches after returning back into monitored voltage range and exceeding fixed hysteresis . In case of failure of two or three phases, the relay is deactivated immediately regardless of the set delay t2.

    Phase sequence
    Monitors correctness of phase sequence. In case of unwanted change output contact breaks. In case of energization of a device with incorrect phase sequence, contact stays opened.

    Asymmetry
    Rate of assymetry between individual phases is set in a range of 5-15 %. In case set asymmetry is exceeded, output relay breaks and LED indicating asymetry shines. Delays t1, t2 and hysteretic are applicable when returning to normal state.